DRAFT - REPORT IN PROGRESS - will be finalized at the end of the shift
Upon arrival, I found the ITF locked and in SCIENCE mode.
At 6:05 UTC I set the MAINTENANCE mode.
DRAFT - REPORT IN PROGRESS - will be finalized at the end of the shift
Upon arrival, I found the ITF locked and in SCIENCE mode.
At 6:05 UTC I set the MAINTENANCE mode.
ITF in Science mode for all the shift.
Guard tours (time in UTC)
From 21:00 to 21:30; from 23:00 to 23:30; from 1:30 to 2:00; from 3:30 to 4:00
In this afternoon shift science mode stopped from 15:35UTC to 18:30UTC for daily calibration and commissioning (RIN coupling vs MICH and PRCL offsets), the ITF unlocked at 15:58UTC with a DOWN command from my ITF_LOCK client, I missclicked on the metatron client instead to set DOWN the CALI node I did it for ITF_LOCK without realizing it; the relock was a bit longer with three fails two locking at CARM_NULL_1F and one meanwhile locking the OMC (#64183).
-guard tours(UTC):
17:11 --> 17:39
19:03 --> 19:30
Air Conditioning
from 14:50UTC the MC building air conditioning started to malfunction with a little increasing of the hall temperature (see plot); experts aware of the problem, an extraordinary maintenance of the system is foreseen for tomorrow.
Calibration
- 15:36UTC: CALIBRATING_DF_DAILY;
Shift started with a couple of unlocks.
17:56 UTC turned off MICH SET loop (putting MICH_SET_CAL to zero)
MICH set loop had not converged, so PSTAB was not yet at zero.
18:00 UTC (5min) PRCL set = 8.0 to zero the frequency to amplitude conversion on B2.
18:06 UTC (5min) PRCL set = 8.0, MICH set = -5.0, to increase PSTAB to DARM coupling
18:13 UTC (5min) PRCL set = 0.0, MICH set = -5.0
18:23 UTC (5min) PRCL set = 0.0, MICH set = 12.0 to zero the PSTAB to DARM coupling
18:29 putting back MICH SET loop (cali at -100000)
Figure 1. I have noticed any changes in the sensitivity during this test, appart from the 157Hz bump getting smaller when changing the MICH set to zero the PSTAB to DARM coupling. To be checked more carrefully if MICH set is really the cause.
Figure 2. Summarizes the change in PRCL and MICH offset. A PRCL offset of 8 changes the PSTAB to DARM coupling by about the same amount as a change of MICH offset of 5.
https://git.ligo.org/virgo/commissioning/commissioning-tasks/-/issues/52
Today during the lock acquisition I have noticed that there was power on B1 PD1 while trying to lock the OMC.
Figure 1 shows fluctuation on B1 PD1 even though the voltage bias is off.
Pressing the close button of the shutter in vpm worked to close it, but before that I panicked and closed B1 PD3 and turned off its voltage bias instead. Which caused an unlock first as DET_MAIN has seen the B1 PD3 being turned off and put the interferometer in DOWN.
Maybe the B1 PD shutters are starting to be stuck again because the interferometer locks are becoming too long, and they are not open/closed often enough. We may need to add checks in the automation to check they are indeed closed.
The DCP measurement is likely just a witness of something else changing.
Figure 1 shows the same as on Paolo's figure, the optical gain changes from 3e9 to 2.9e9 and the DCP frequency changes by ~5Hz.
Figure 2 shows the squeezing test of last week. The SR TY set point was changed intentionally by ~25Hz, and the optical gain changed from 3e9 to 2.85e9.
So the change in DCP that occured during the weekend could explain only ~30% of the change in optical gain.
From the recent long lock, one can notice that two small drops of the range happen together with drops of the optical gain. At the same time, the double cavity pole measured by Hrec increases a bit, while the one measured by ACL is kept constant by SR_TY loop. A possible guess is that the error signal of SR_TY loop is sometimes slightly corrupted by something which does not affect the DCP computation done by Hrec. The effect would be eventually a little change of SR_TY working point and a consequent increase of the actual DCP, together with an increase of mystery noise. But we should also consider the possibility that the optical gain is changing because of something else and the measurement of DCP is just a witness of that. We should check if a change of DCP by 4 Hz can explain the visible drop of optical gain, or usually a larger DCP variation is required.
I would also add that maybe we could acquire some day of data at a lower DCP setting, in order to check if the current setting is still the one which maximizes the range.
The DCP measurement is likely just a witness of something else changing.
Figure 1 shows the same as on Paolo's figure, the optical gain changes from 3e9 to 2.9e9 and the DCP frequency changes by ~5Hz.
Figure 2 shows the squeezing test of last week. The SR TY set point was changed intentionally by ~25Hz, and the optical gain changed from 3e9 to 2.85e9.
So the change in DCP that occured during the weekend could explain only ~30% of the change in optical gain.
Today at 13:00 LT we could see an airplane flying over the main building, probably just departed from the lane nearby; one minute later it can be spotted in the CEB microphone signals, but it did not have an impact on Hrec; some 25 minutes later it probably came back along the same route, luckily causing no effect again on the sensitivity.
ITF found in LOW_NOISE_3_SQZ and in Science Mode. It kept the lock for the whole shift.
Sub-system reportsDAQ
From around 10:39 UTC the process ELE_QGBT was reported as not responding on VPM (Orange State) and as not working on DMS (red flag). At 10:46 UTC I restarted the process via VPM to restore the nominal condition.
In a similar way to how the PRC gain is computed using the phase camera, I computed the dark port transfer function of the carrier using the B1p phase camera data.
I used 10 mins of the single bounce data during the OMC calibration as Pref and looked at 10mins of data after 1 hour of science mode (Pscience). The dark port transfer function for the carrier is then: TF = Pscience/Pref*Tprm*Tbs*Rinput*Tbs*Tsrm
Using the values from the OptChar page:
Tprm = 0.04835; Tsrm = 0.396; Tbs = 0.5; Rinput = 1-0.01377;
The dark port transfer function is shown after 1 hour of science run is shown in figure 1.
Using the input power (17 W), we can estimate the carrier power in the dark port, shown in figure 2. On average, after 1 hour of science mode the carrier power at the dark port was 0.0884 W, versus 0.1034 at the start of science mode.
ITF in Science mode for all the shift
Software
At 22:27 UTC I stopped and restarted the process ELE_QGBT because it was not running porperly.
Guard tours (time in UTC)
from 21:50 to 23:20; from 00:00 to 00:30; from 2:00 to 2:30; from 3:50 to 4:20
ITF found in LOW_NOISE_3_SQZ and in Science Mode. It kept the lock for the whole shift.
Guard Tours (UTC):
5:01 - 5:28
7:01 - 7:30
9:11 - 9:38
11:01 - 11:30
I found ITF in SCIENCE; It remained locked for the whole shift.
ITF found in Science.
At 15:14 UTC the DMS reported a jump in the power DAS OUT; I immediately contacted the TCS on-call. From remote Ilaria adjusted the TCS WI chiller setpoint and thanks to this operation we could recover the standard value of the power DAS OUT without breaking Science mode (see entry 64172.
At 20:34 UTC ITF in Calibration for the planned calibrations (the planned starting time was delayed by LIGO):
At 21:05 UTC ITF back in Science mode.
No DMS alerts in the shift.
Francesco called me because of the change of state of WI CO2 laser.
To restore the standard condition, I adjusted the WI chiller set point from 19.04 degrees to 19.05 degrees (15.40 UTC).
The BCK chiller set point has been chaged accordingly.
The ITF kept science mode all the shift.
- guard tours(UTC):
5:11 --> 5:39
6:59 --> 7:25
11:10 --> 11:38
Other
FCEM_MotSwitch crashed and restarted at 8:22UTC.
I found ITF in SCIENCE; It remained locked for the whole shift.
ITF found in Science mode.
At 19:15 UTC the Squeezing was disengaged and the ITF exited from Science mode. Unfortunately, the ITF switched out of Science mode while I was at dinner; when I returned, I checked the cameras and the main screens of the control room and the ITF resulted locked and in standard condition thus I assumed that it was still in Science mode; I realized after a few minutes that we weren't in Science mode.
At 20:02 UTC I re-engaged the Squeezing and then I set Science mode 20:02 UTC.
Software
Guard tours (time in UTC)
From 17:15 to 17:45; from 20:05 to 20:35.
Following the issue on ALS flip mirror in the early morning (Entry 64161), 2 new flags have been implemented for the DMS in order to monitor them. Configuration inside the VPM process have been done and will be reload during Tuesday maintenance to be made effective.
Tuesday 30th of April a slow cold FSR scan has been performed (LOGBOOK n°64135). Here is the report of the analysis concerning the estimation of the finesse of both north and west Fabry-Perot cavities. On each of the 12 FSR scans, an Airy peak has been fitted. From those fits, the FSR and the width at half maximum have been estimated allowing us to derive the finesse. Then we took the average of all the results. Values obtained for each cavities are summarized below :
B7 : average finesse 463.16 standard deviation 2.99
B8 : average finesse 447.59 standard deviation 4.04
Figure 1 shows one example of fit for both north and west scan. For each example, the fit is shown on the full scan and zoomed on the first TEM00 mode. As it can be seen, the data are very noisy. Nevertheless, this can not explain why results are asymmetric between north and west cavities.
Here is the quick analysis of the OMC lock and scan performed by the operator during the last maintenance:
https://logbook.virgo-gw.eu/virgo/?r=64135
Fig.1 shows the OMC lock. We reach about 13.7 uW of power on B1_PD3 when the OMC is locked on the carrier TEM00.
Fig.2 and Fig.3 show the OMC scan in temperature. The first order mode peak is about 14% of the TEM00 peak, which is not a very good alignment (this means that the offsets used for NI single bounce are not well tuned), but sufficient for this type of sanity check.
One of the reason for having a CARM SLOW control is the OMC. If there are fluctuations in CARM the OMC length needs to follow, and with higher CARM fluctuation the OMC lock RMS will become worse and increase the thermorefractive coupling. However, this is seems to be very far from limiting.
Figure 1 shows the current noise budget (May 3 early afternoon), and the magenta line is the OMC length noise projection. about a factor 100 below the sensitivity curve.
Figure 2 shows last night when the ground motion was large (and presumably CARM RMS worse), the OMC length noise projection is still about a factor 20 below the sensitivity curve.
Figure 3 before the reduction in the CARM SLOW loop gain the OMC length noise projection was so low that it did not show on the figure.
So my impression is that if needed the CARM SLOW loop gain could be reduced by another factor 2. But there might be other aspects of the interferometer than the OMC that require a low CARM RMS.
The ITF kept the lock all the shift, from 5:00UTC the sensitivity started to worsening and the BNS range went down to 35Mpc, this is because of at the relock the end green beams was not flipped out, I did it by hand to recover the standard sensitivity, science mode stopped from 5:13UTC to 5:17UTC.
Sub-system reportsAir Conditioning
eurothermServer2 stopped and restarted at 7:58UTC because of missing data from FCEM air conditioning system.
Other
FCEM_MotSwitch crashed and restarted at 8:30UTC.
Yesterday the gain of CARM SLOW has been reduced by almost a factor of 2, in order to restore its normal stability, but obviously also its accuracy has been reduced. I looked for recent data with similar seismic, suspension and TMs motion (fig 1, fig 2); RFC error signal with the two different gains is compared in fig 3. The required accuracy is not clear to me: having a number, we could design a proper filter. We need also to take into account the noise projection of this loop towards Hrec. The noise injection performed yesterday has been analysed: we can see in fig 4 that at 20 Hz the projection is a bit too close to the sensitivity (DARM is totally limited by this noise in a wide region - fig 5). With the gain used in the past days, the projection would become too close, so an eventual request of more accuracy would require a better shaping of the control filter, or a better noise subtraction.
One of the reason for having a CARM SLOW control is the OMC. If there are fluctuations in CARM the OMC length needs to follow, and with higher CARM fluctuation the OMC lock RMS will become worse and increase the thermorefractive coupling. However, this is seems to be very far from limiting.
Figure 1 shows the current noise budget (May 3 early afternoon), and the magenta line is the OMC length noise projection. about a factor 100 below the sensitivity curve.
Figure 2 shows last night when the ground motion was large (and presumably CARM RMS worse), the OMC length noise projection is still about a factor 20 below the sensitivity curve.
Figure 3 before the reduction in the CARM SLOW loop gain the OMC length noise projection was so low that it did not show on the figure.
So my impression is that if needed the CARM SLOW loop gain could be reduced by another factor 2. But there might be other aspects of the interferometer than the OMC that require a low CARM RMS.